The soft starter has very little to no impact on the harmonic emissions in the line as it simply acts as a bypass switch during running mode. A soft-start lasts barely 0.3-0.5 seconds. So, the resultant harmonics emissions will simply reflect any inherent load current harmonics from the AC unit/heat pump.